I have installed the Compaq UPS agents but some of the UPS options are grayed out in the Compaq Insight Manager

OpenServer 5.0.0OpenServer 5.0.2OpenServer 5.0.4OpenServer 5.0.5OpenServer 5.0.6OpenServer 5.0.7UnixWare 7.0.0UnixWare 7.0.1UnixWare 7.1.0UnixWare 7.1.1UnixWare 7.1.3UnixWare 7.1.4

Written · Last revised

Problem

I have installed the Compaq UPS agents but some of the UPS options are grayed out in the Compaq Insight Manager.

NOTE:     An issue with the Compaq UPS agent leaking streams memory has been
          identified and reported to Compaq for investigation and resolution.
          This problem can be identified by the 'freekv' value decreasing
          steadily over time.  The freekv value can be displayed by
          running the 'sar -r' command if the sar system activity data
          collection and performance monitoring utility is enabled.  If this
          is not enabled then occasionally running the command 'sar -r 1 1'
          and comparing the freekv values taken during the day will confirm
          whether this problem is happening.
          Current recommendation is to remove the Compaq UPS monitoring agent
          software unless this is really necessary for operation of the server.
          Removal can be done by issuing the command 'pkgrm cpqups'.

Cause

The Compaq Insight Manager and the Compaq UPS agent are not correctly
communicating.  This may be due to the a corruption during the
installation of either package or the versions of each product may not
fully support each other.

Solution

Following are three steps necessary to ensure that both versions are correct:

1. Re-install the latest Compaq Insight Manager (CIM) agent for
   the Compaq UPS.  These are available from:
https://www.hpe.com
2. Install the latest Compaq Insight Manager software on your
   Windows client.  This is also available from:
https://www.hpe.com

3. Check the CIM console because at this stage, under Recovery button, UPS button should be active now!

If not then, the Compaq Power Management (CPQCPM) Insight plug-in must be installed in the CIM console on the PC.

To do this:

a) Close Compaq Insight Manager Console if it is running. b) On the CIM Management CD go to directory \cpqcpm\insight\eng and run setup.exe c) Reboot the PC where CIM Console is installed. d) After reboot you will be able to see full details about the UPS

NOTE:     In order to ensure that "root" receives messages regarding power
          outage, you must configure messages to be sent to "root" when power
          has been removed and restored from the UPS "Alert Handling" icon
          within the Compaq Insight Manager program.

See also

ta112481, "How do I install the Compaq Insight Manager on OpenServer?"

ta111742, "How do I install the Compaq Insight Manager on UnixWare 7?"

From the Xinuos technical article database, record 113701. Reproduced with permission. The original is at www.sco.com/ta/113701, which is reachable but blocked from search engines. Xinuos marks this article against a retired product line. That refers to the product’s lifecycle, not to whether the advice still works — plenty of it still applies to running systems.

Next step

Need this fixed rather than explained?

Tell us the release, what the system runs and what it is doing. We will reply by email with what we would do next.

  • You deal with the people who do the work
  • No obligation, and no upgrade required before we will help
  • We tell you plainly if something is not worth doing

Send an enquiry

We reply by email. If a server is down, say so in the first line. You can also write to help@scoexpert.com.